1.Cylinder Control unit- Integral design requires no seperate release pressure
cylinder -
seperate wire cable activation lines for automatic fusible link and optional remote
pull station
provide an added measure of safety - an easily accessible manual release mechanism
which
provides an option to the automatic fusible link and, depending on local codes,
can be used in place of a remote manual pull station - unique fool proof technique
for achieving necessary
input wire cable tension
2. Piping- Unbalanced piping network simplifies application design and installation
- no seperate piping to connect system pressure cylinders to extinguishing agent
container. Schedule 40 stainless, chrome - plated and black pipe can be used
3. Cylinders (DOT-4B-175 rated) - Contain Pyro-Chem Potassium Carbonate Solution
stored at 175 psig - pressure gauge for visual maintenance checks - 2.40, 3.50,
and 5.50 gallon sizes provide 8, 13, and 20 flow point coverage respectively, offering
a broad range of application coverage.
4. Nozzles - fixed and Swivel head nozzles have been established to relax
placement tolerances.
5. Remote Manual Pull Station - Simple operating instructions with a double
action release avoids careless system discharge - a 100' wire cable run with 1/16
inch cable and 17 corner pulleys maximum or 3/64 inch cable and 20 corner pulleys
maximum allows mounting flexibility - a dedicated wire cable input line to the cylinder
control head provides a true back-up in the event thermal links are fouled.
6. Fusible Link Kits - Accomodates both series and terminal placement to
minimize inventory and simplify ordering - all necessary components included for
efficient assembly and installation - a 350 degrees F fusible link standard - other
temperatures available - 15 fusible links on a 100' wire cable run with 20 corner
pulleys maximum provides substantial hazard coverage.
7. Automatic Gas Shut-Off Valve - Complies with requirements pertaining to
the shut-off fuel as described by NFPA 17A - after regular maintenance/service check
can be reset at control head for convenience of service technician - a 50' wire
cable run with 15 corner pulleys maximum provides mounting flexibility.
8. Corner Pulleys and Accessories - Designed to ensure reliable system function,
as tested by Underwriters Laboratories.
|